List of Property Enumeration Sets for BV Objects
Please refer to the specific installation guide of each controller for a detailed overview on each property listed
Object Name
Object Type
Thermostat Range / Indexes
AI1 Configuration
Boolean Writable
falseText=None,trueText=CO2
AO2 Lock Status
Boolean Point
falseText=Inactive,trueText=Active
AO2 RA/DA
Boolean Writable
falseText=Direct Acting,trueText=Reverse Acting
Auto Fan
Boolean Writable
falseText=Auto Speed,trueText=Auto Speed / Auto Demand
Auto Mode Enable
Boolean Writable
falseText=Disabled,trueText=Enabled
Aux Command
Boolean Writable
falseText=Off,trueText=On
Aux Contact
Boolean Writable
falseText=Normally Opened,trueText=Normally Closed
Aux Status
Boolean Point
falseText=Off,trueText=On
BI1 Status
Boolean Point
falseText=Deactivated,trueText=Activated
BI2 Status
Boolean Point
falseText=Deactivated,trueText=Activated
BO5 Contact Function
Boolean Writable
falseText=Normally Opened,trueText=Normally Closed
BO5 Lock Status
Boolean Point
falseText=Inactive,trueText=Active
BO5 Status
Boolean Point
falseText=Off,trueText=On
BO5 Time Base
Boolean Writable
falseText=15 Minutes,trueText=10 Seconds
Comfort Mode
Boolean Writable
falseText=Comfort,trueText=Economy
Compressor Auxiliary Lockout
Boolean Writable
falseText=Off,trueText=On
Config Motion Detection
Boolean Writable
falseText=No PIR,trueText=PIR Cover Present
Control Type
Boolean Writable
falseText=On/Off,trueText=Floating
Cool NO/NC
Boolean Writable
falseText=Normally Closed,trueText=Normally Openend
Cool Stages Lockout Status
Boolean Point
falseText=Off,trueText=On
Cooling Lockout Status
Boolean Point
falseText=Off,trueText=On
Cooling Valve Status
Boolean Point
falseText=Off,trueText=On
Dehumidification Lockout
Boolean Writable
falseText=Disabled,trueText=Enabled
Dehumidification Lockout Functions
Boolean Writable
falseText=Disabled,trueText=Enabled
Dehumidification Output Status
Boolean Point
falseText=Off,trueText=On
Dehumidification Status
Boolean Point
falseText=Off,trueText=On
DI Status
Boolean Point
falseText=Deactivated,trueText=Activated
DI1 Status
Boolean Point
falseText=Deactivated,trueText=Activated
DI2 Status
Boolean Point
falseText=Deactivated,trueText=Activated
Direct Reverse Acting
Boolean Writable
falseText=Direct Acting,trueText=Reverse Acting
Discharge Air Alarm
Boolean Point
falseText=Off,trueText=On
Discharge Temperature Alarm
Boolean Point
falseText=Off,trueText=On
Display Scale
Boolean Writable
falseText=C,trueText=F
Fan Control
Boolean Writable
falseText=Off,trueText=On
Fan Lock Alarm
Boolean Point
falseText=Off,trueText=On
Fan Options
Boolean Writable
falseText=On Heat,trueText=Auto Heat
Fan Purge Delay
Boolean Writable
falseText=Off,trueText=On
Filter Alarm
Boolean Point
falseText=Off,trueText=On
Frost Alarm
Boolean Point
falseText=Off,trueText=On
Frost Protection
Boolean Writable
falseText=Off,trueText=On
G Fan Status
Boolean Point
falseText=Off,trueText=On
Heat NO/NC
Boolean Writable
falseText=Normally Closed,trueText=Normally Openend
Heat Stages Lockout Status
Boolean Point
falseText=Off,trueText=On
Heating Lockout Status
Boolean Point
falseText=Off,trueText=On
Heating Valve Status
Boolean Point
falseText=Off,trueText=On