Wiring of Local Inputs to VTR73xxA Terminal Equipment Controller
Wiring of Remote Inputs to VC3504E & 3404E Relay Packs
VTR73xxA
Terminal Controller
13 - BI 1
14 - Scom
15 - BI 2
Local BI 1 Input by configuration:
- None ( monitoring only
)
- Remote motion detector: Motion NO or Motion
NC
- Remote Night Setback:
RNSB
- Window contact: Window
Local BI 2 Input by configuration:
- None ( monitoring only
)
- Door contact: DoorDry
VC30x04E
Relay Pack
OR
4 - RUI1
5 - Scom
6 - RBI2
7 - SS
8 - RS
Remote RUI 1 Input by configuration:
- None ( monitoring only )
- Local changeover sensor ( 10K type2 COS )
- Local changeover contact ( COC NO or COC NC )
- Service alarm ( Service )
- Filter Alarm ( Filter )
Remote RBI 2 Input by configuration:
- None ( monitoring only )
- Service alarm ( Service )
- Filter Alarm ( Filter )
SS Supply sensor:
-
10K type2
monitoring only
- Auto dectected
RS Return Air Sensor:
-
10K type2
main temperature copntrol
i
- Auto dectected ( by-passes VTR73xxA internal sensor )