15 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Typical examples of a 2 event ofce schedule
Ex. #1 Ofce building closed all weekend
Event Period #1 - Event #1 Period #1 - Event #2
Occupied Unoccupied
Setpoint
Cool
72 °F
Heat
70 °F
Cool
80 °F
Heat
62 °F
Daily
Occupancy
Monday 7.00 AM 6.00 PM Day time only
Tuesday 7.00 AM 6.00 PM Day time only
Wednesday 7.00 AM 6.00 PM Day time only
Thursday 7.00 AM 6.00 PM Day time only
Friday 7.00 AM 6.00 PM Day time only
Saturday 12.00 PM * 12.00 PM * Unoccupied
Sunday 12.00 PM * 12.00 PM * Unoccupied
* Programming consecutive events to the same time will cause the thermostat to choose
the last event as the time at which it will set its schedule. In the above example, the
thermostat will control to the unoccupied set point until 7:00 AM Monday.
Ex. #2 Ofce building open all weekend
Event Period #1 - Event #1 Period #1 - Event #2
Occupied Unoccupied
Setpoint
Cool
72 °F
Heat
70 °F
Cool
80 °F
Heat
62 °F
Daily
Occupancy
Monday 7.00 AM 6.00 PM Day time only
Tuesday 7.00 AM 6.00 PM Day time only
Wednesday 7.00 AM 6.00 PM Day time only
Thursday 7.00 AM 6.00 PM Day time only
Friday 7.00 AM 6.00 PM Day time only
Saturday 12.00 AM 11.59 PM ** Occupied
Sunday 12.00 AM 11.59 PM ** Occupied
** To program a day as occupied for 24 hours, set that day Occupied time to 12:00 AM and
Unoccupied time to 11:59 PM There will be a 1 minute unoccupied period every night at
11:59 PM with this schedule conguration.
Note: 12:00 PM = Noon
12:00 AM = Midnight