6 | VZ7656E1000W Installation Guide
TERMINAL, IDENTIFICATION AND FUNCTION
Wiring
Output for cooling / compressor stage
number 2.
Output for cooling / compressor stage
number 1.
Power supply of controller, hot side
(Delivered from the RTU).
Power supply of controller, common side.
Also used as reference for the analog BPD
output when used (Delivered from the RTU).
24 VAC switched leg for the heating stages.
If heating stages are part or RTU,
install a jumper across RC & RH.
If heating stages are part of separate
equipment with a different power
supply, feed external switched power
leg through RH without installing a
jumper across RC & RH.
Output for heating stage number 1.
Output for heating stage number 2.
Local analog 0 - 10 VDC by-pass damper /
VFD output.
0-10 VDC analog fresh air damper /
economizer output.
Local analog 0 – 5 VDC static pressure
input.
0-10 VDC analog input for airflow transmitter
Return air temperature sensor input. If
sensor fails, controller will use the on-board
thermistor sensor to control if the
communication is lost.
Reference input for DI 1, RS, OS & DS.
Outside air temperature sensor input.
Discharge air temperature sensor input.