Viconics VTR8300 Line Voltage Application Guide Bedienungsanleitung Seite 17

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 23
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 16
VTR8300 Fan Coil ControllerApplication Guide
17
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: ( 514) 321-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), valve opens to
maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), valve opens
to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.
Wired Window Switch
The window switch automatically locks out heating/cooling when
window opens.
Options
• BACnet
®
and Wireless communication models available (see
Appendix B for network wiring).
• Models available with factory installed PIR sensor.
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• Binary inputs can be configured to control occupancy via door
or window contact, remote night setback, or provide alarms for
service or filter monitoring.
• Universal input can be configured for changeover sensor.
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
1
2
3
4
5
6
7
8
BACnet+
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
Tx / Rx
7 VDC
Com
BI1 (Window)
SCom