PROPERTY VALUE RANGE RESTRICTIONS FOR AV OBJECTS
Object Name Object Type Instance
Minimum
Range Value
Maximum
Range Value
Default Value
Heating Setpoint Limit AV 58 40°F (4.5°C) 90°F (32°C) 90°F (32°C)
Cooling Setpoint Limit AV 59 54°F (12°C) 100°F (37.5°C) 54°F (12°C)
Temporary Occupancy Time AV 62 0H 24H 2H
Minimum Deadband AV 63 2°F (1°C) 5°F (2.5°C) 2°F (1°C)
Proportional Band AV 65 3°F (1.2°C) 10°F (5.6°C) 3°F (1.2°C)
Standby time AV 67 5H 24H 5H
Unoccupied Time AV 68 0H 24H 0H
Calibrate Outside Temp. Sensor AV 74 - 5°F(2.5°C) 0°F (0°C)
Number of Cooling Stages AV 75 1 2 2
Power-up Delay AV 76 10 s 120 s 10 s
Economizer Minimum Position AV 78 0% 100% 0%
Economizer Maximum Position AV 81 0% 100% 100%
Heating CPH AV 84 3 8 4
Cooling CPH AV 85 3 8 4
Anti Short Cycle Timer AV 86 0 min 5 min 2 min
Number of Heating Stages AV 87 0 2 2
Heating Demand Limit AV 88 0% 100% 0%
Cooling Demand Limit AV 89 0% 100% 0%
Heat Lock AV 91 -15°F (-26°C) 120°F (49°C) 120°F (49°C)
Cool Lock AV 93 -40°F (-40°C) 125°F (52°C) -40°F (-40°C)
Supply Air Setpoint AV 94 50°F (10°C) 90°F (32°C) 55°F (13°C)
Changeover Setpoint AV 95 14°F (-10°C) 70°F (21°C) 55°F (13°C)
Fresh Air Range Upper Limit AV 96 0 ft
3
20000 ft
3
0 ft
3
Minimum Supply Heat AV 97 50°F (10°C) 72°F (22°C) 64°F (18°C)
Supply Heat Lockout AV 98 -15°F (-26°C) 120°F (49°C) 32°F (0°C)
Discharge High Limit AV 99 70°F (21°C) 150°F (65.5°C) 120°F (49°C)
Room Temperature AV 100 -40°F (-40°C) 122°F (50°C) N/A
Outdoor Temperature AV 101 -40°F (-40°C) 122°F (50°C) N/A
Supply Temperature AV 102 -40°F (-40°C) 122°F (50°C) N/A
CO2 Level AV 106 0 ppm 2000 ppm 0 ppm
Air Flow Level AV 107 0 ft
3
20000 ft
3
0 ft
3
UI19 Status AV 108 0% 100% 0%