VT8600 Series
Installation Guide
7
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: ( 514) 321-4150
028-0435-01
www.viconics.com February 2015
© 2015 Viconics Technologies. All rights reserved.
REMOTE SENSOR ACCESSORIES
Model no. Description
S3010W1045 Wall mounted temperature sensor
S3020W1045 Wall mounted temperature sensor with override button and occupancy status LED
Note:
If one or multiple sensor(s) is/are connected into the RS terminal, the internal temperature sensor is automatically disabled. Dis-
connecting the sensor(s) in RS terminal will re-activate the internal sensor.
Remote mount temperature sensors inputs use 10K type 2 NTC thermistors.
Features:
• Each sensor can be configured for various averaging combinations
• Optional occupancy led
• Optional override key
Wiring example of single remote room sensor:
VT8600
Series Controller
1xS3020W1000
Remote wiring 1 sensor
S2-1= On, S2-2=On
S3010W1000
Remote wiring 1 sensor
S2-1= On, S2-2=On
SCom
RS
Aux
C
DI
OR
Dip switch setting for 1 sensor
S2-1= On, S2-2=On
SCom
RS
Common
UI 20 - RS
B0 1 - AUX
C (Common)
UI 16
UI 17
ON
1 2