VT8300 Series
User Interface Guide
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
UI 16
Universal input no.1 configuration
Default value = None
Universal Input No. 1
None: no function associated with input
Rem NSB: remote NSB timer clock input. The scheduling gets set as
per the binary input and provides low cost setback operation via a dry
contact.
Motion No and Motion NC: advanced PIR occupancy functions using
a Normally Open (NO) or Normally Closed (NC) remote PIR motion
sensor.
Window EMS: forces system to disable any current heating or
cooling action by Terminal Equipment Controller.
UI 17
Universal input no.2 configuration
Default value = None
Universal Input No. 2
None: no function associated with input.
Door Dry: door contact and motion detector.
Override: temporary occupancy remote override contact.
Filter: backlit flashing filter alarm shows on the Terminal Equipment
Controller LCD screen when the input is energized.
Service: backlit flashing Service alarm shows on Terminal Equipment
Controller LCD screen when input is energized.
1/7 Configuration
UI 19
UI 17
UI 16
None
None
None
Occupancy src
Motion
Smart recovery
Off
Setpoint func.
Attach Stp
CONFIGURATION PARAMETERS SCREEN 1//7