Seitenansicht 8
9
VST5000W5000W Wireless Survey Tools User Guide
Please note that this ONLY applies to the initial network
start-up. Once all the devices are online to the Niagara
database, everything will operate seamlessly even on
powerup/down&networkre-starts.
How Orphan nodes are created in the eld.
Ex.: 2 small buildings are within a few feet of each other.
Bothhave6+devices/nodes/controllereach(fig.12).
A possible cause for Building B orphan nodes is as follow:
Building A is rst stated and sets the Jace – coordinator
conguration parameters for the PAN ID and Channel.
Premises:
• BuildingAisrststated.
• Yellowdevice/node/controllerhasgivenoutits6
addresses out to other devices in building A.
• BuildingBdevices/nodes/controllerscanonlybe
connectedthroughbluedevice/nodes/controller
duetomaximumdistancecoverage.
Result:
• BecauseBluecontrollercannothaveanaddress
assigned by Yellow controller to join the network.
TheallOrangedevices/nodes/controllerscannot
join the ZigBee network either.
Getting orphan devices back on the network:
• DisconnectandbringoneofthebuildingB
device/node/controllersandpoweritupin
building A until it joins the ZigBee network
( conrmed either at the Jace – coordinator
or using the status LED on the wireless
communicationcardofthedevice/node/
controller).
• Whenthedevice/node/controllerhasjoined
the network in building A and is added to the
Niagara database, bring it back into building
B so it can propagate ZigBee addresses to the
other devices in building B.
Within Range
Jac
e
t t
t t
t t
t t
t t
t t
t t
Jace
Building A Building B
Fig. 12
5H stands for 5 hops maximum
ANYgivendevice/node/controllershouldbe
optimized” to be NO FURTHER than 5 Hops to and from
theJace/Coordinator.Thisisduetothenatureofthe
Viconics ZigBee stack in the wireless controllers.
To properly layout the architecture and
determine the number of Jaces required
on the job site, begin by establishing the
maximumpossiblecoverageofasingle
Jace with a wireless communication card
respectingthe5hopmaximumrule.This
can also done with the survey tools and
is covered in detail in the manual for the
survey procedures and tool usage: MAN
VWG-SURVEY-Exx.
1. Begin by positioning the Jace-coordinator centrally
in the oor space you are working in.
2. Find the coverage radius of the coordinator (VWG
or Jace-Driver) at its proposed location. Its possible
that another location may improve your network
performance or that you may require an additional
coordinator ( VWG or Jace-Driver ) or additional
REP5000W wireless repeaters.
3. Set survey tool A at the proposed coordinator (VWG
or Jace-Driver)
4. With survey tool B, walk about the oor where a
cluster of controllers are to be found. Locate the
boundary where the signal strength is about 20%.
Thisrepresentsthemaximumradiusofthersthop
where connectivity is possible based on the building
environment and partition construction.
Please note that this distance can be anywhere from
NIL to hundreds of feet (fig. 13).
A
B
Jace
Coordinator
Proposed
location
Cluster of:
devices / nodes / controllers
Cluster of:
devices / nodes / controllers
20%
Fig. 13