7. OPERATION:
WHEN POWER IS FIRST APPLIED TO A FACTORY UNIT:
The display will show [888] and the 3 status LED’s will come on for 4 seconds and then go off for 1 second.
The pump will go on and then the actual water temperature will be displayed.
Factory settings of main parameters:
Pool setpoint: OFF
Spa setpoint: OFF
Filtration time FIL: 8 hours per day
The actual temperature displayed is held in memory and displayed for 5 minutes until the water temperature sensor has sampled
circulating water. After that delay of 5 minutes, the displayed temperature is automatically updated and displayed.
CONFIGURING THE UNIT J1 JUMPER
The unit can control 2 different setpoints:
The pool temperature and the Spa temperature.
2 methods can be used to switch the unit between ( Pool setpoint Mode ) or ( Spa setpoint Mode ).
How to activate either ( Pool setpoint Mode ) or ( Spa setpoint Mode )
J1 jumper not cut
Using the select key will active either mode manually ( press the or to switch between ( P_S )
J1 jumper cut A remote Spa flow switch connected on CN19 will activate ( Spa setpoint Mode ) **
** Notes:
In this mode using the select key will authorize changing the Pool or Spa setpoint, but the actual mode is determined by the Spa
flow switch connected on CN19.
The Pool LED or Spa LED on the display will confirm which mode is active.
ADJUSTING POOL & SPA SETPOINTS:
Setpoint ranges:
Controller configured in °F Controller configured in °C
Pool setpoint:
OFF 61°F to 95°F OFF 16°C to 35°C
Spa setpoint:
OFF 61°F to 104°F OFF 16°C to 40°C
The control is shipped with setpoints at OFF in Pool and Spa mode.
The heatpump is automatically switched OFF if a setpoint below 61 °F is selected.
In the off mode the control will display the water temperature.
Use the select and arrow key to enter Pool or Spa mode.
Use the arrow to increase the setpoint above 61 °F on the selected mode.
The pool heater ( heatpump compressor ) is automatically authorized to operate if a setpoint above 61 °F is selected.
Adjust the setpoints to required value.
TURNING THE POOL HEATER ON ( HEATPUMP COMPRESSOR ):
When there is a demand for heat.
In Pool mode: If the actual water temperature is lower than the desired Pool setpoint temperature.
In Spa mode: If the Spa mode is manually selected ( J1 in place )
Or if the Spa flow switch is energized ( J1 cut )
And if the actual water temperature is lower than the desired Spa setpoint temperature.
When heatpump is energized:
The Heat On LED is energized.
The compressor will come on.
The fan will come on as dictated by coil temperature.
Heat will stay on until setpoint is satisfied.